Errors and Troubleshooting
SolarEdge Installation Guide – MAN-01-00002-1.6
103
Error #
LCD
Description Troubleshooting
13 AC Current
Surge
AC current surge. The
internal hardware that
measures AC current
has measured
substantially high
output currents. This
may occur because of
changes in the AC
voltage or a switching
load near the
If this fault persists:
Check the AC connection to inverter.
Ask the grid operator whether a large
surge source or irregular load exists
near the installation site.
If the grid does not have problems
contact SolarEdge support.
14 AC Voltage
Too High
AC voltage surge. The
internal hardware that
measures AC voltage
has measured
substantially high
instantaneous output
voltage.
If this fault persists:
Check the AC connection to inverter.
Ask the grid operator whether a large
surge source or irregular load exists
near the site.
Verify that the output wire size
matches the distance between the
inverter and the location of the grid
connection.
Use a larger gauge wire for the AC
output.