46
N-
o.
Cable
Type
Specification
Outer
diameter
Cross section
3 DC cable
Outdoor multi-core copper
wire cable
Complying with 1,000V
and 30A standard
6 ~ 9 mm 4 ~ 6 mm²
4
AC cable *
Outdoor multi-core copper
wire cable
14 ~ 25 mm 6 ~ 10 mm²
5 12 ~ 14 mm 4 ~ 6 mm²
6
Communica-
tion cable
Shielded twisted pair
5.3 ~ 7 mm
2 * (0.5 ~ 1.0) mm²
CAT 5E outdoor shielded
network cable
8 * 0.2 mm²
7
Additional
Grounding ca-
ble *
Outdoor single-core cop-
per wire cable
The same as that of the PE wire in
the AC cable
* If local regulations have other requirements for cables, set the cable specification accord-
ing to the local regulations.
The factors that affect cable selection include rated current, cable type, routing mode, ambi-
ent temperature, and maximum expected line loss.
The cabling distance between the battery and the inverter should be less than 10 m, and
within 5 m is recommended.
Backup Wiring Diagram(Australia and New Zealand)
The neutral cable of GRID side and BACK-UP side must be connected together according
to the wiring rules AS/NZS_3000. Otherwise BACK-UP function will not work.
NO. SH5.0/6.0RT/8.0/10RT SH5.0/6.0RT/8.0/10RT-20
①
40A/600V DC breaker *
②
32A/400V AC breaker
③
25A/400V AC breaker
6 Electrical Connection User Manual