User Manual 8 Troubleshooting and Maintenance
75
2. Wait a moment for system recovery
or restart the system.
Battery precharge voltage
fault.
1. The inverter can normally be
connected to the grid but
charge/discharge has stopped.
2. Check the battery port voltage and
the battery communication cable
connection.
3. Force a shutdown and restart the
inverter and battery system.
4. Wait a moment for system recovery
or restart the system.
Battery under-voltage
fault.
Battery cell voltage
imbalance fault.
Battery cable connection
fault.
Low SOH (State of
Health) warning.
1. The inverter can normally be
connected to the grid and the
charge/discharge function is normal.
2. Batteries are beyond the scope of
the warranty. It is recommended to
contact the distributor for
replacements.
Battery over-voltage
warning.
1. The inverter can normally be
connected to the grid. Charge has
stopped but discharge is allowed.
2. The system will resume after a
certain time of discharging.
Battery over-temperature
warning.
1. The inverter can normally connected
be to the grid but charge/discharge has
stopped.
2. Check the ambient temperature of
the battery location.
3. Wait a moment for system recovery
or restart the system.
Battery
under-temperature
warning.
Battery
charging/discharging
over-current warning.
1. The inverter can normally be
connected to the grid but
charge/discharge has stopped.
2. Wait a moment for system recovery
or restart the system.
Battery tray voltage
imbalance warning.
1. The inverter can normally be
connected to the grid and the
charge/discharge functions are normal.
2. Check whether the cable connection
of the battery is correct.
Battery under-voltage
warning.
1. The inverter can normally be
connected to the grid. Discharge has
stopped but charge is allowed.
2. The system will resume after a
certain time of charging.
Battery internal warning.
Consult the battery manufacturer for a
solution.