TMSL 097-44018-26 Issue 2: Sep 99
Page 152
COMMAND CODE: REPT EVT
PURPOSE
REPORT EVENT
This message reports the occurrence of nonalarmed events, including the access identifier, the severity
of the alarm, the type of condition, whether it affects service, and a short description of the alarm.
MESSAGE FORMAT
<sid> <date> <time>
A <atag> REPT EVT {EQPT|PORT}
"<aid>:<condtype>,<condeff>,<ocrdat>,<ocrtm>:
/* <conddescr> */" ...
;
Note: All the parameters between the quotation marks will appear on a single line (the parameters are
shown on two lines here due to space restrictions). Refer to Table A and Table F for parameter values.
EXAMPLE
SANJOSE-114 1997-12-08 15:41:32
A 2 REPT EVT PORT
"MRC-1-4:LOS,SC,12-06,04-22-45:
/* REFERENCE INPUT SIGNAL LOSS */"
;
This example, tagged as automatic message 2, shows that a standing condition has been raised be-
cause of a loss of an external input to port 4 of MRC 1 which occurred on Dec 6 at 4:22:45 AM.

Table of Contents

Other manuals for Symmetricom TimeProvider 500 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 500 series and is the answer not in the manual?

Symmetricom TimeProvider 500 series Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 500 series
CategoryData Loggers
LanguageEnglish

Related product manuals