EasyManuals Logo

Symmetricom XLi User Manual

Symmetricom XLi
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
106 XLi Time & Frequency System
XLi-man, Issue 8, 6/17/2008, Rev. H
SSSSSSSSSSSS SSSSSSSSSS SSSSSSS S SSS S SSSSS S
1
F73 MASK
XLi replies:
F73 MASK DDE-EEEEEEEEEEDDDDD
To view the Time Threshold setting, enter:
F73<S>THRESHOLD<CR>
XLi replies:
F73<S>THRESHOLD<S><nanoseconds><S>ns<CR><LF>
where <nanoseconds> is the time error threshold in nS
To set a new Time Threshold, enter a new value for
<nanoseconds> (Range 0 to 99,999 nS), as follows:
F73<S>THRESHOLD<SEP><nanoseconds><CR>
XLi replies:
OK<CR><LF>
To view Timeout Delay, enter:
F73<S>TIMEOUT<CR>
XLi replies:
F73<S>TIMEOUT<SEP><seconds><S>s<CR><LF>
To enter a new Time Delay, enter a value for <seconds> (Range 0 to 86,400 nS), as follows:
F73<S>TIMEOUT<SEP><seconds><CR>
XLi replies:
OK<CR><LF>
To enable LED Blink, enter:
F73<S>BLINK<SEP> ENABLE<CR>
XLi responds:
OK<CR><LF>
To disable LED Blink, enter:
F73<S>BLINK<SEP> DISABLE<CR>
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com