166 XLi Time & Frequency System
XLi-man, Issue 8, 6/17/2008, Rev. H
SSSSSSSSSSSS SSSSSSSSSS SSSSSSS S SSS S SSSSS S
1
128 = function number.
<SP> = ASCII space character one or more.
B = ASCII character to denote Option Bay number follows
<N> = Option Bay Number, 1 through 10.
TFOM = ASCII string for TFOM output format request.
<LT> = line terminator; for output strings (a carriage return and line feed ) or for input strings (a
carriage return only).
Sample request: F128 B2 TFOM<CR><LF>
Response: F128 B2 TFOM ENABLE <CR><LF>
To change the Have Quick Time Figure of Merit output enable/disable selection, send the following send
the following string to the Serial/Network port:
F128<SP>B<N><SP>TFOM<SP><OUT><LT>
where:
F = ASCII character F.
128 = function number.
<SP> = ASCII space character.
B = ASCII character to denote Option Bay number follows
<N> = Option Bay Number, 1 through 10.
TFOM = ASCII character to denote “Time Figure of Merit” selection.
<OUT>= TFOM Output selection, ENABLE or DISABLE
<LT> = line terminator; for output strings (a carriage return and line feed ) or for input strings (a
carriage return only).
Sample entry: F128 B2 TFOM ENABLE<CR>
Response: OK<CR><LF>
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom XLi and is the answer not in the manual?

Symmetricom XLi Specifications

General IconGeneral
BrandSymmetricom
ModelXLi
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals