50 44 1670 001-GB-I
HDA eco
It can be necessary to change the value after the calibration of the measuring system.
How the measuring system can be calibrated see section 3.2.
5.3.4.2.3 Post Decimals
Display (e.g.):
The number of decimal points displayed after dispensing can be displayed and
changed here.
You can choose between ‘0’ and ‘1’.
5.3.4.2.4 Automat Lock
Display (e.g.):
Here you can set if the automatic dispenser should be blocked for refuelling or ena-
bled again after having been blocked.
You can choose between ‘yes’ and ‘no’.
5.3.4.2.5 Device Address
Display (e.g.):
The device address is necessary for the joint operation of several HDA eco units con-
nected to one serial port (e.g. RS422).
A value between 0 and 9 can be entered.
5.3.4.2.6 Max Zero Refuellings
Several sequential refuelling events that were completed with a dispensing quantity
below 500 ml (‘zero refuelling’) indicate a system error, e.g. lack of fuel, defective
pump or meter.
Display (e.g.):
When a value different from 0 has been set for ‘max. zero refuellings’ the HDA eco
blocks automatically after the adjusted number of consecutive zero refuelling oc-
curred. A blocked HDA eco can be enabled again via the corresponding menu in the
device once the cause for zero refuellings has been eliminated (see section 5.3.4.2.4).
A value of 0 deactivates the blocking function. Values from 0 to 98 can be entered.
Post decimals
◄►1
Automat lock
◄►No
Device address
0
Max. Zero dsp.
5