4-18
Group 00 Basic Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
00-00 Control Mode Selection
0: V/F
0 - O O O *3
1: Reserved
2: SLV
3~4: Reserved
5: PM SLV
00-01 Motor’s Rotation Direction
0: Forward
0 - O O O *1
1: Reverse
00-02
Main Run Command Source
Selection
0: Keypad
1
- O O O
1: External Terminal (Control
Circuit)
2: Communication Control
(RS-485)
3: PLC
4: RTC
00-03
Alternative Run Command
Source Selection
0: Keypad
0
- O O O
1: External Terminal (Control
Circuit)
2: Communication Control
(RS-485)
3: PLC
4: RTC
00-04
Language Selection (for LCD
only)
0: English
0 - O O O
1: Simple Chinese
2: Traditional Chinese
3: Turkish
00-05
Main Frequency Command
Source Selection
0: Keypad
1 - O O O
1: External Terminal (Analog AI1)
2: Terminal Command UP/ DOWN
3: Communication Control
(RS-485)
4: Reserved
5: Reserved
6: RTC
7. AI2 Auxiliary Frequency *7
00-06
Alternative Frequency
Command Source Selection
0: Keypad
0 - O O O
1: External Terminal (Analog)
2: Terminal Command UP/ DOWN
3: Communication Control
(RS-485)
4: Reserved
5: Reserved
6: RTC
7. AI2 Auxiliary Frequency *7
00-07
Main and Alternative
Frequency Command Modes
0: Main Frequency
0 - O O O
1: Main Frequency + Alternative
Frequency
00-08
Communication Frequency
Command Range
0.00-599.00 (Note8) 0.00 Hz O O O
00-09
Communication Frequency
Command Memory Selection
0: Do not save when power is off.
0 - O O O
1: Save when power is off.