4-19
Group 00 Basic Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
00-10 Minimum frequency detection
0: Show warning if lower than
minimum frequency
1: Run as minimum frequency if
lower than minimum frequency
0 - O O O Note2
00-11
Selection of PID Lower Limit
Frequency
0: PID is bound to lower limit
frequency when inverter sleeps.
0 - O O O
Note1
1: PID is bound to 0Hz when
inverter sleeps.
00-12 Upper Limit Frequency 0.1~109.0 100.0 % O O O
00-13 Lower Limit Frequency 0.0~109.0 0.0 % O O O
00-14 Acceleration Time 1 0.1~6000.0 - s O O O *1
00-15 Deceleration Time 1 0.1~6000.0 -
s O O O *1
00-16 Acceleration Time 2 0.1~6000.0 - s O O O *1
00-17 Deceleration Time 2 0.1~6000.0 -
s O O O *1
00-18 Jog Frequency 0.00~599.00 (Note8) 6.00 Hz O O O *1
00-19 Jog Acceleration Time 0.1~0600.0 - s O O O *1
00-20 Jog Deceleration Time 0.1~0600.0 -
s O O O *1
00-21 Acceleration Time 3 0.1~6000.0 - s O O O *1
00-22 Deceleration Time 3 0.1~6000.0 -
s O O O *1
00-23 Acceleration Time 4 0.1~6000.0 - s O O O *1
00-24 Deceleration Time 4 0.1~6000.0 -
s O O O *1
00-25
Switch-Over Frequency of
Acc/Dec Time 1 and Time 4
0.0~599.00 (Note8) 0.0 Hz O O O
00-26 Emergency Stop Time 0.1~6000.0 5.0 s O O O
00-27 Reserved
00-28
Main Frequency Command
Characteristic Selection
0: Positive Characteristic
(0~10V/4~20mA is
corresponding to 0~100%)
0 - O O O
1: Negative Characteristic
(0~10V/4~20mA is
corresponding to 100~0%)
00-29
~
00-31
Reserved
00-32 Application Selection Presets
0: General
0 - O O O
1: Water Supply Pump
2: Conveyor *7
3: Exhaust fan
4: HVAC
5: Compressor *7
6: Reserved
7: Reserved
00-33
Modified Parameters (only for
LCD)
0: Enable
0 - O O O
1: Disable
00-34
~
00-40
Reserved