4-20
Group 00 Basic Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
00-41 User Parameter 0
Set 13-06 = 1, and enable user
parameter.
Setting Range: 00-01 ~24-17, but
except 00-41~00-56 and group 17
(only used in LCD keypad)
- O O O
00-42 User Parameter 1 - O O O
00-43 User Parameter 2 - O O O
00-44 User Parameter 3 - O O O
00-45 User Parameter 4 - O O O
00-46 User Parameter 5 - O O O
00-47 User Parameter 6 - O O O
00-48 User Parameter 7 - O O O
00-49 User Parameter 8 - O O O
00-50 User Parameter 9 - O O O
00-51 User Parameter 10 - O O O
00-52 User Parameter 11 - O O O
00-53 User Parameter 12 - O O O
00-54 User Parameter 13 - O O O
00-55 User Parameter 14 - O O O
00-56 User Parameter 15 - O O O
Group 01 V/F Control Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
01-00 V/F Curve Selection 0~FF F - O X X *3
01-01 Reserved
01-02 Maximum Output Frequency 4.8~599.00 (Note8)
50.0/
60.0
Hz O O O *6*8
01-03 Maximum Output Voltage
200V: 0.1~255.0 -
V O X X *8
400V: 0.2~510.0 -
01-04 Middle Output Frequency 2 0.0~599.00 (Note8) 0.0 Hz O X X
01-05 Middle Output Voltage 2
200V: 0.0~255.0
0.0 V O X
X
*8
400V: 0.0~510.0
01-06 Middle Output Frequency 1 0.0~599.00 (Note8) 30.0 Hz O X
X
01-07 Middle Output Voltage 1
200V: 0.0~255.0 38.5
V O X X *8
400V: 0.0~510.0 77.0
01-08 Minimum Output Frequency 0.0~599.00 (Note8) 1.5 Hz O O O
01-09 Minimum Output Voltage
200V: 0.0~255.0 6.6
V O X X *8
400V: 0.0~510.0 13.2
01-10 Torque Compensation Gain 0.0~2.0 0.5 - O X X *1
01-11
Selection of Torque
Compensation Mode
0: Torque Compensation Mode 0
0 - O X X
Note1
1: Torque Compensation Mode 1
01-12 Base Frequency 4.8~599.00 (Note8)
50.0/
60.0
Hz O O O *8
01-13 Base Output Voltage
200V: 0.0~255.0 -
V O X X *8
400V: 0.0~510.0 -
01-14 Input Voltage Setting
200V: 155.0~255.0 -
V O O O *8
400V: 310.0~510.0 -
01-15 Torque Compensation Time 0~10000 200 ms O X X