4-21
Group 02 IM Motor Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
02-00 No-Load Current 0.01~600.00 KVA A O X X
02-01 Rated Current
25%~200% of inverter’s rated
current.
KVA A O O X
02-02 Reserved
02-03 Rated Rotation Speed 0~60000 KVA Rpm O O X
02-04 Rated Voltage
200V: 50.0~240.0 -
V O O X *8
400V: 100.0~480.0 -
02-05 Rated Power 0.01~600.00 KVA kW O O X
02-06 Rated Frequency 4.8~599.00 (Note8)
50.0/
60.0
Hz O O X *8
02-07 Poles 2~16 (Even) 4 pole- O O X *6
02-08 Reserved
02-09 Excitation Current 15.0~70.0 KVA % X O X
02-10 Core Saturation Coefficient 1 1~100 KVA % X O X
02-11 Core Saturation Coefficient 2 1~100 KVA % X O X
02-12 Core Saturation Coefficient 3 80~300 KVA % X O X
02-13 Core Loss 0.0~15.0 KVA % O X X
02-14 Reserved
02-15 Resistance between Wires 0.001~60.000 KVA Ω O O X
02-19 No-Load Voltage
200V: 50~240
KVA V X O X
400V: 100~480
02-20
~
02-32
Reserved
02-33 Leakage Inductance Ratio 0.1~15.0 KVA % X O X
02-34 Slip Frequency 0.10~20.00 KVA Hz X O X
Group 03 External Di
ital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
03-00
Multi-function Terminal
Function Setting-S1
0: 2-Wire Sequence
(ON: Forward Run Command)
0
-
O O O
1: 2-Wire Sequence
(ON: Reverse Run Command)
O O O
03-01
Multi-function Terminal
Function Setting-S2
2: Multi-Speed Setting Command 1
1
O O O
3: Multi-Speed Setting Command 2
O O O
4: Multi-Speed Setting Command 3
O O O
03-02
Multi-function Terminal
Function Setting-S3
5: Multi-Speed Setting Command 4
2
O O O
*6
6: Forward Jog Run Command
O O O
03-03
Multi-function Terminal
Function Setting-S4
7: Reverse Jog Run Command
3
O O O
*6
8: UP Frequency Increasing
Command
O O O
03-04
Multi-function Terminal
Function Setting-S5
9: DOWN Frequency Decreasing
Command
4
O O O
*6
10: Acceleration/ Deceleration
Setting Command 1
O O O
11: Acceleration/ Deceleration
Inhibition Command
O O O