4-22
Group 03 External Di
ital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
03-05
Multi-function Terminal
Function Setting-S6
12: Main/Alternative Run command
Switching
17
O O O
13: Main/Alternative Frequency
Command Switching
14: Emergency Stop
(Decelerate to Zero and Stop)
15: External Base block Command
(Rotation freely to Stop)
16: PID Control Disable
17: Fault Reset (RESET)
18: Reserved
-
- - -
19: Speed Search 1(from the
maximum frequency)
O O X
20: Manual Energy Saving Function
17
O X X
21: PID Integral Reset O O O
22~23: Reserved - - -
24: PLC Input
O O O
25: External Fault
26: 3-Wire Sequence
(Forward/ Reverse Command)
27: Local/ Remote Selection
28: Remote Mode Selection
29: Jog Frequency Selection
30: Acceleration/ Deceleration
Setting Command 2
31: Inverter Overheating Warning
32: Reserved - - -
33: DC Braking O X X
34: Speed Search 2
(from Frequency Command)
O X O
35: Timing Function Input
O O O
36: PID Soft Start Disable
37~40: Reserved - - -
41: PID Sleep O O O
42~46: Reserved - - -
47: Fire Mode (Forced to Run
Mode)
O O O
48: KEB Acceleration O X X
49: Parameters Writing Allowable O O O
50: Unattended Start Protection
(USP)
O O O
51~52: Reserved - - -
53: 2-Wire Self Holding Mode (Stop
Command)
O O O
54: Switch PID1 and PID2
55: RTC Time Enable
56: RTC Offset Enable
57: Forced Frequency Run
58: Run Permissive Function
63: switch to Tolerance Range of
Constant Pressure 2
64: Reserved
- - -