4-23
Group 03 External Di
g
ital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
65: Short-circuit braking
X X O
66~67: Reserved
- - -
68: Ext. Fault 2 (Note6)
O O O
69: Ext. Overload (Note6)
O O O
03-06
~
03-07
Reserved
03-08 (S1~S6) DI Scan Time
0: Scan Time 4ms
1: Scan Time 8ms
1 - O O O
03-09
Multi-Function Terminal
(S1-S4 Selection)
xxx0b:S1 A Contact
xxx1b:S1 B Contact
0000b - O O O
xx0xb:S2 A Contact
xx1xb:S2 B Contact
x0xxb:S3 A Contact
x1xxb:S3 B Contact
0xxxb:S4 A Contact
1xxxb:S4 B Contact
03-10
Multi-Function Terminal
(S5-S6 Selection)
xxx0b:S5 A Contact
xxx1b:S5 B Contact
0000b - O O O
xx0xb:S6 A Contact
xx1xb:S6 B Contact
x0xxb: Reserved
x1xxb: Reserved
0xxxb: Reserved
1xxxb: Reserved
03-11 Relay (R1A-R1C) Output
0: During Running
1 - O O O *6 1: Fault Contact Output
2: Frequency Agree
03-12 Relay (R2A-R2C) Output
3: Setting Frequency Agree
(03-13 ± 03-14)
0 -
O O O
*6
4: Frequency Detection 1
(03-13+03-14)
O O O
5: Frequency Detection 2
(03-13+03-14)
O O O
6: Automatic Restart O O O
7~8: Reserved - - -
9: Baseblock O O O
10~11: Reserved - - -
12: Over-Torque Detection
O O O
13: Current Agree *7
14: Mechanical Brake Control
(03-17~18)
Note1
O O O
15~17: Reserved - - -
18: PLC Status
O O O
19: PLC Control
20: Zero Speed
21: Inverter Ready
22: Undervoltage Detection
23: Source of Operation Command
24: Source of Frequency Command
25: Low Torque Detection
26: Frequency Reference Missing
27: Timing Function Output