4-26
Group 04 External Analog Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
04-00 AI Input Signal Type
0: AI1: 0~10V
AI2: 0~10V
1 - O O O
1: AI1: 0~10V
AI2: 4~20mA
2: Reserved
3: Reserved
4: AI1: 4~20mA
AI2: 0~10V
*9
5: AI1: 4~20mA
AI2: 4~20mA
*9
04-01
AI1 Signal Scanning and
Filtering Time
0.00~2.00 0.03 s O O O
04-02 AI1 Gain 0.0~1000.0 100.0 % O O O *1
04-03 AI1 Bias -100.0~100.0 0 % O O O *1
04-04 Negative AI
0: Disable
0 - O O O
Note6
1: Enable
04-05 AI2 Function Setting
0: Auxiliary Frequency
0 -
O O O
1: Frequency Reference Gain O O O
2: Frequency Reference Bias O O O
3: Output Voltage Bias O X O
4: Coefficient of Acceleration and
Deceleration Reduction
O
O O
5: DC Braking Current O O X
6: Over-Torque Detection Level O O O
7: Stall Prevention Level During
Running
O
X X
8: Frequency Lower Limit O O O
9: Jump Frequency 4 O O O
10: Added to AI1 O O O
11: Positive Torque Limit X O O
12: Negative Torque Limit X O O
13: Regenerative Torque Limit X O O
14: Positive / Negative Torque
Limit
X O
O
15: Reserved - - -
16: Torque Compensation X O X
17: Reserved - - -
04-06
AI2 Signal Scanning and
Filtering Time
0.00~2.00 0.03 s O O O
04-07 AI2 Gain 0.0~1000.0 100.0 % O O O *1
04-08 AI2 Bias -100.0~100.0 0 % O O O *1
04-09
AI Input Signal Type of I/O
card
0: AI3:0~10V
1: AI3:-10~10V
2: AI3:4~20mA
0 - O O O *10
04-10 AI3 Function Setting
Range and definition are the same
as those of 04-05
10 - O O O *10