4-27
Group 04 External Analog Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
04-11 AO1 Function Setting
0: Output Frequency
0 -
O O O
1: Frequency Command O O O
2: Output Voltage O O O
3: DC Voltage O O O
4: Output Current O O O
5: Output Power O O O
6: Motor Speed O O O
7: Output Power Factor O O O
8: AI1 Input O O O
9: AI2 Input O O O
10: Torque Command X O O
11: q-axis Current X O O
12: d-axis Current X O O
13: Speed deviation X X O
14: Reserved - - -
15: ASR Output X X O
16: Reserved - - -
17: q-axis Voltage X O O
18: d-axis Voltage X O O
19~20: Reserved - - -
21: PID Input O O O
22: PID Output O O O
23: PID Target Value O O O
24: PID Feedback Value O O O
25: Output Frequency of the Soft
Starter
O O O
26~27: Reserved - - -
28: Communication Control *6 O O O
04-12 AO1 Gain 0.0~1000.0 100.0 % O O O *1
04-13 AO1 Bias -100.0~100.0 0 % O O O *1
04-14
~
04-15
Reserved
04-16 AO2 Function Setting
Setting range and definition are the
same as 04-11
3 - O O O
04-17 AO2 Gain 0.0~1000.0 100.0 % O O O *1
04-18 AO2 Bias -100.0~100.0 0 % O O O *1
04-19 AO Output Signal Type
0: AO1:0~10V AO2:0~10V
0 O O O
1: AO1:0~10V AO2:4~20mA
2: AO1:4~20mA AO2:0~10V
3: AO1:4~20mA AO2: 4~20mA
04-20 Filter Time of AO Signal Scan 0.00~0.50 0.00 s O O O
*1
*7
04-21
AI3 S
ignal Scanning and
Filtering Time
0.00~2.00 0.03 s O O O *10
04-22
AI3 Gain
0.0~1000.0 100.0 % O O O *10
04-23
AI3 Bias
-100.0~100.0 0 % O O O *10

Table of Contents