EasyManua.ls Logo

TECO F510 series - Group 08 Protection Parameters

TECO F510 series
555 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-35
Group 08 Protection Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
08-00 Stall Prevention Function
xxx0b: Stall prevention is enabled
in acceleration.
0000b - O O O
xxx1b: Stall prevention is disabled
in acceleration.
xx0xb: Stall prevention is enabled
in deceleration.
xx1xb: Stall prevention is disabled
in deceleration.
x0xxb: Stall prevention is enabled
in operation
x1xxb: Stall prevention is disabled
in operation
0xxxb: Stall prevention in operation
decelerates based on
deceleration time 1
1xxxb: Stall prevention in operation
decelerates based on
deceleration time 2
08-01
Stall Prevention Level in
Acceleration
20~200 120 % O O O
08-02
Stall Prevention Level in
Deceleration
200V: 330~410 385
V O O O
400V: 660~820 770
08-03
Stall Prevention Level in
Operation
30~200 120 % O X X
08-04 Reserved
08-05
Selection for Motor Overload
Protection (OL1)
xxx0b: Motor Overload Protection
is disabled
0001b - O O O
xxx1b: Motor Overload Protection
is enabled
xx0xb: Cold Start of Motor
Overload
xx1xb: Hot Start of Motor Overload
x0xxb: Standard Motor
x1xxb: Special motor
0xxxb: Reserved
1xxxb: Reserved
08-06
Start-up Mode of Overload
Protection Operation (OL1)
0: Stop Output after Overload
Protection
0 - O O O
1: Continuous Operation after
Overload Protection.
08-07
Motor Overload (OL1)
Protection Level
0: Motor overload (OL1) Protection
0
0 - O O O
Note3
1: Motor overload (OL1) Protection
1
2: Motor overload (OL1) Protection
2

Table of Contents

Other manuals for TECO F510 series

Related product manuals