Group 08 Protection Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
08-08
utomatic Voltage Regulation
(AVR)
0: Enable
0 - O O O
1: Disable
08-09
Selection of Input Phase Loss
Protection
0: Disable
0 - O O O
1: Enable
08-10
Selection of Output Phase
Loss Protection
0: Disable
0 - O O O
1: Enable
08-11
~
08-12
Reserved
08-13
Selection of Over-Torque
Detection
0: Over-Torque Detection is
Disabled.
0 - O O O
1: Start to Detect when Reaching
the Set Frequency.
2: Start to Detect when the
Operation is Begun.
08-14
Selection of Over-Torque
Operation
0: Deceleration to Stop when Over-
Torque is Detected.
0 - O O O
1: Display Warning when Over-
Torque is Detected. Go on
Operation.
2: Coast to Stop when Over Torque
is Detected
08-15
Level of Over-Torque
Detection
0~300 150 % O O O
08-16
Time of Over-Torque
Detection
0.0~10.0 0.1 Sec O O O
08-17
Selection of Low-Torque
Detection
0: Low-Torque Detection is
Disabled.
0 - O O O
1: Start to Detect when Reaching
the Set Frequency.
2: Start to Detect when the
Operation is Begun.
08-18
Selection of Low-Torque
Operation
0: Deceleration to Stop when Low-
Torque is Detected.
0 - O O O
1: Display Warning when Low-
Torque is Detected. Go on
Operation.
2: Coast to Stop when Low-Torque
is Detected
08-19
Level of Low-Torque
Detection
0~300 30 % O O O
08-20 Time of Low-Torque Detection 0.0~10.0 0.1 Sec O O O
08-21
Limit of Stall Prevention in Acc
over Base Speed
1~100 50 % O O O
08-22
Stall Prevention Detection
Time in Operation
2~100 100 ms O O O
08-23 Ground Fault (GF) Selection 0: Disable 0 - O O O