4-37
Group 08 Protection Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
1: Enable
08-24
Operation Selection of
External Fault
0: Deceleration to Stop
0 - O O O 1: Coast to Stop
2: Continuous Operation
08-25
Detection selection of
External Fault
0: Immediately Detect when the
Power is Supplied.
0 - O O O
1: Start to Detect during Operation
08-26
~
08-29
Reserved
08-30
Selection of Run Permissive
Function
0: Deceleration to Stop
0 - O O O
1: Coast to Stop
08-31
~
08-34
Reserved
08-35
Fault Selection of Motor
Overheat
0: Disable
0 - O O O 1: Deceleration to Stop
2: Coast to Stop
08-36
Time Coefficient of PTC Input
Filter
0.00 ~ 5.00 2 Sec O O O
08-37 Fan Control Function (Note)
0: Start at Operation
0 - O O O 1: Permanent Start
2: Start at High Temperature
08-38 Delay Time of Fan Off 0~600 60 Sec O O O
08-39
Delay Time of Motor Overheat
Protection
1~300 60 Sec O O O
08-42 PTC Trip Level 0.1~10.0 0.7 V O O O
Note1
08-43 PTC Reset Level 0.1~10.0 0.3 V O O O
Note1
08-45 PTC Disconnection Detection
0: Disable
0 - O O O
Note3
1: Warning
2: Fault
08-46
Temperature Agree Level
0~254°C 0
°C
O O O
Note6
08-47
Temperature Reset Level
0~254°C 0
°C
O O O
Note6
08-48
Selection of Fire Mode
0: Disable
1: Enable
0 - O O O
Note6
08-49
Multi-Function Input Terminal
Status of Fire Mode
0:Reset after Power Off
1:Reset after Terminal Removed
0 - O O O
Note6
08-50
Multi-Function Terminal
Status of Fire Mode
XXX0b: S6 A contact
XXX1b: S6 B contact
0000b - O O O
Note6
08-51
Motor Speed Setting Source
of Fire Mode
0:Fire Mode Speed(08-52)
1:PID Control
2:AI2
0 - O O O
Note6
08-52
Motor Speed of Fire Mode
0.00~100.00 100.00 % O O O
Note6
08-53
PID Detection Level of Fire
Mode
0~100 0 % O O O
Note6
08-54
Delay Time of Fire Mode PID
Loss
0.0~10.0 1.0 s O O O
Note6