4-38
Group 08 Protection Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
08-55
PID Feedback Loss Detection
Selection of Fire Mode
0:Keep Running
1:Fire Mode Speed (08-52)
2:Maximum Output Frequency
(01-02)
1 - O O O
Note6
08-56
Detection Level of Fire Mode
AI2 Signal
0.0~100 80.0 % O O O
Note6
08-57
Delay Time of Fire Mode AI2
Signal Loss
0.0~10.0 1.0 s O O O
Note6
08-58
Selection of Fire Mode AI2
Signal Loss
0:Keep Running
1:Fire Mode Speed (08-52)
2:Maximum Output Frequency
(01-02)
1 - O O O
Note6
08-59
Fire Mode Motor Direction
0:Forward
1:Reverse
0 - O O O
Note6
08-60
Fire Mode Password
00000~65534 0 - O O O
Note6
Note: 1. Standard H & C type, IP20 frame 6~9 do not have this function.
2. Enhanced E & G type, IP20 frame 6~8 do not have “Start at High Temperature” function.
3. Enhanced E & G type, IP20 frame 9 do not have this function.
Group 09: Communication Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
09-00
INV Communication Station
Address
1~31 1 - O O O *2
09-01
Communication Mode
Selection
0: MODBUS
0 - O O O
1: BACNET
2: METASYS
3: PUMP in Parallel Connection
09-02 Baud Rate Setting (bps)
0:1200
4 - O O O
*2
*6
1:2400
2:4800
3:9600
4:19200
5:38400
09-03 Stop Bit Selection
0:1 Stop Bit
0 - O O O *2
1: 2 Stop Bit
09-04 Parity Selection
0: No Parity
0 - O O O *2 1: Even Bit
2: Odd Bit
09-05
Communications Data Bits
Selection
0: 8 bits data
0 - O O O
Note1
1: 7 bits data
09-06
Communication Error
Detection Time
0.0~25.5 0.0 S O O O