4-44
Group 11: Auxiliary Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
11-49
~
11-50
Reserved
11-51
Braking Selection of Zero
Speed
0: Disable
0 - O X X
1: Enable
11-52
~
11-53
Reserved
11-54
Initialization of Cumulative
Energy
0: Do not Clear Cumulative Energy
0 - O O O *1
1: Clear Cumulative Energy
11-55 STOP Key Selection
0: Stop Key is Disabled when the
Operation Command is not
Provided by Keypad.
1 - O O O
1: Stop Key is Enabled when the
Operation Command is not
Provided by Keypad.
11-56 UP/DOWN Selection
0: When UP/DOWN in Keypad is
Disabled, it will be Enabled if
Pressing ENTER after
Frequency Modification.
0 - O O O
1: When UP/DOWN in Keypad is
Enabled, it will be Enabled upon
Frequency Modification.
11-57 Reserved
11-58 Record Reference Frequency
0: Disable
0 - O O O *1
1: Enable
11-59 Gain of Preventing Oscillation 0.00~2.50 0.01 O X X *7
11-60
Upper Limit of Preventing
Oscillation
0~100 30 % O X X *7
11-61
Time Parameter of
Preventing Oscillation
0~100 0 O X X *7
11-62
Prevention of Oscillation
Selection
0: Mode 1
1: Mode 2
2: Mode 3
1 O X X *7
11-63 Flux-Strengthening Selection
0: Disable
1 X O X
Note1
1: Enable
11-64
Acceleration Speed Gain
Adjustment
0.1~10.0 1.0 - O X X
Note3
11-65 Target Main Circuit Voltage
200V: 200V~400V 370
- O X X
Note3
400V: 400V~800V 740
11-66
2 Phase/ 3 Phase PWM
Switch Frequency
6.00~60.00 20 Hz O O X
Note3
11-67
Detection Range at Soft PWM
Function 2
0~12000 0 Hz X O O
Note3
11-68
Detecting Start Frequency at
Soft PWM Function 2
6.00~60.00 20 Hz X O O
Note3
11-69 Gain of Preventing Oscillation 0.00~200.00
5.00
%
O
X X
Note2