4-43
Group 11: Auxiliary Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
11-29 Auto De-rating Selection
0: Disable
0 - O X X
1: Enable
11-30
Variable Carrier Frequency
Max. Limit
2~16 KVA
*a
KHz O X X
11-31
Variable Carrier Frequency
Min. Limit
1~16 KVA
*a
KHz O X X
11-32
Variable Carrier Frequency
Proportional Gain
00~99 00 - O X X
11-33
Rise Amount of DC Voltage
Filter
0.1~10.0 0.1 Vdc O X X
Note4
*1
11-34
Fall Amount of DC Voltage
Filter
0.1~10.0 5.0 Vdc O X X
Note4
*1
11-35
Dead band Level of DC
Voltage Filter
0.0~99.0 10.0 Vdc O X X
Note4
*1
11-36
Frequency Gain of OV
Prevention
0.000~1.000
0.050
-
O
X X
Note2
*1
11-37
Frequency Limit of OV
Prevention
0.00~599.00 (Note8)
5.00
Hz
O
X X
Note2
11-38
Deceleration Start Voltage of
OV Prevention
200V: 200~400V
400V: 400~800V
200V:
300
400V:
700
V
O
X X
Note2
11-39
Deceleration Stop Voltage of
OV Prevention
200V: 300~400V
400V: 600~800V
220V:
350
440V:
750
V
O
X X
Note2
11-40
OV Prevention Selection
0: Disable
1: OV Prevention Mode 1
2: OV Prevention Mode 2
3: OV Prevention Mode 3
0 -
O
X X
Note2
11-41
Reference Frequency Loss
Detection
0: Deceleration to Stop when
Reference Frequency
Disappears
0 - O O O
1: Operation is Set by 11-42 when
Reference Frequency
Disappears
11-42
Reference Frequency Loss
Level
0.0~100.0 80.0 % O O O
11-43 Hold Frequency at Start 0.0~599.00 (Note8) 0.0 Hz O O O
11-44 Frequency Hold Time at Start 0.0~10.0 0.0 s O O O
11-45 Hold Frequency at Stop 0.0~599.00 (Note8) 0.0 Hz O O O
11-46 Frequency Hold Time at Stop 0.0~10.0 0.0 s O O O
11-47 EB Deceleration Time 0.0~25.5 0.0 s O X X *1
11-48 KEB Detection Level
200V: 190~210 200
V O X X
400V: 380~420 400