4-42
Group 11: Auxiliary Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
11-00 Direction Lock Selection
0: Allow Forward and Reverse
Rotation
1 - O O O
1: Only Allow Forward Rotation
2: Only Allow Reverse Rotation
11-01 Carrier Frequency
0: Carrier Output Frequency Tuning
KVA
*a
- O O O
1: 1~16: 1~16KHz
11-02 Soft PWM Function Selection
0: Disable
1(V/f)
0(SLV&
PMSLV)
- O O O 1: Soft PWM Function 1
2: Soft PWM Function 2
11-03
Automatic carrier lowering
selection
0: Disable
0 - O X X
1: Enable
11-04
S-curve Time Setting at the
Start of Acceleration
0.00~2.50 0.20 s O O O
11-05
S-curve Time Setting at the
End of Acceleration
0.00~2.50 0.20 s O O O
11-06
S-curve Time Setting at the
Start of Deceleration
0.00~2.50 0.20 s O O O
11-07
S-curve Time Setting at the
End of Deceleration
0.00~2.50 0.20 s O O O
11-08 Jump Frequency 1 0.0~599.00 (Note8) 0.0 Hz O O O
11-09 Jump Frequency 2 0.0~599.00 (Note8) 0.0 Hz O O O
11-10 Jump Frequency 3 0.0~599.00 (Note8) 0.0 Hz O O O
11-11 Jump Frequency Width 0.0~25.5 1.0 Hz O O O
11-12 Manual Energy Saving Gain 0~100 80 % O X X
11-13 Automatic Return Time 0~120 60 Sec O O O *6
11-14
~
11-17
Reserved
11-18
Manual Energy Saving
Frequency
0.00~599.00 (Note8) 0.00 Hz O X X
11-19
Automatic Energy Saving
Function
0: Disabled
0 - O X X
1: Enabled
11-20
Filter Time of Automatic
Energy Saving
0~200 140 ms O X X
11-21
Voltage Upper Limit of Energ
Saving Tuning
0~100 100 % O X X
11-22
Adjustment Time of
Automatic Energy Saving
0~5000 20 ms O X X *1
11-23
Detection Level of Automatic
Energy Saving
0~100 10 % O X X
11-24
Coefficient of Automatic
Energy Saving
0.00~655.34 KVA
*a
- O X X
11-25
~
11-27
Reserved
11-28
Frequency Gain of
Overvoltage Prevention 2
1~200 100 % O X X
Note4