4-41
Group 10: PID Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
10-35 PID Unit
0: %
0 - O O O *6
1: FPM
2: CFM
3: PSI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: KPa
Note4
10-36 PID2 Proportional Gain (P) 0.00~10.00 3.00 - O O O *1
10-37 PID2 Integral Time (I) 0.0~100.0 0.50 s O O O *1
10-38 PID2 Differential Time (D) 0.00~10.00 0.00 s O O O *1
10-39
PID Output Frequency Setting
during disconnection
00.00~599.00 (Note8) 30.00 Hz O O O *6
10-40
Compensation Frequency
Selection of PID Sleep
0: Disable
0 - O O O
Note1
1: Enable
10-41
~
10-43
Reserved
10-44 Precharge Frequency 0.0~120.0 0 Hz O O O
Note3
10-45 Precharge Time 0~250 0 Sec O O O
Note3
10-46 Precharge Target Level 0~10000 0 - O O O
Note3
10-47 Proportional Gain 3(P) 0.00~10.00 3.00 O O O
Note6
10-48 Integral Time 3(I) 0.00~100.00 0.50
Sec
O O O
Note6
10-49 Differential Time 3(D) 0.00~10.00 0.00
Sec
O O O
Note6