4-52
Group 13 Maintenance Function Group
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
13-07 Parameter Password Function 00000~65534 00000 - O O O
13-08 Restore Factory Setting
0: No Initialization
0 - O O O
2: 2 wire Initialization
(220/440V, 60Hz)
3: 3 wire Initialization
(220/440V, 60Hz)
4: 2 wire Initialization
(230/415V, 50Hz)
5: 3 wire Initialization
(230/415V, 50Hz)
6: 2 wire Initialization
(200/380V, 50Hz)
7: 3 wire Initialization
(200/380V, 50Hz)
8: PLC Initialization
9: 2 Wire Initialization
(230V/460V, 60Hz)
10: 3 Wire Initialization
(230V/460V, 60Hz)
11: 2 wire Initialization,
230V/400V, 60Hz
12: 3 wire Initialization,
230V/400V, 60Hz
13: 2 wire Initialization,
230V/400V, 50Hz
14: 3 wire Initialization,
230V/400V, 50Hz
15: 2 wire Initialization,
(220/380V, 50Hz)
Note4
16: 3 wire Initialization
(220/380V, 50Hz)
Note4
13-09
Fault History Clearance
Function
0: Do not Clear Fault History
0 - O O O *1
1: Clear Fault History
13-10
Parameter Password Function
2
0 ~ 9999 0 O O O
13-11 C/B CPLD Ver. 0.00~9.99 - O O O *7
13-12 Option Card Id 0~255 0 O O O *7
13-13 Option Card CPLD Ver. 0.00~9.99 - O O O *7
13-14 Fault Storage Selection
0: Auto Restart Fault Messages are
not saved in fault history.
1 O O O
Note1
1: Auto Restart Fault Messages are
saved in fault history.
13-15
~
13-20
Reserved
13-21
Previous Fault Message
Display Previous Fault Message - - O O O
Note2