4-60
Group 16: LCD Function Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
16-36 Selection of RTC Speed
0: Off
0 O O O
1: By Timer 1
2: By Timer 2
3: By Timer 3
4: By Timer 4
5: By Timer 1+2
16-37
Selection of RTC Rotation
Direction
xxx0b: RTC Run1 Forward
Rotation
0000b O O O
xxx1b: RTC Run1 Reverse
Rotation
xx0xb: RTC Run2 Forward
Rotation
xx1xb: RTC Run2 Reverse
Rotation
x0xxb: RTC Run3 Forward
Rotation
x1xxb: RTC Run3 Reverse
Rotation
0xxxb: RTC Run4 Forward
Rotation
1xxxb: RTC Run4 Reverse
Rotation
Group 17: IM Motor Automatic Tuning Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
17-00
Mode Selection of Automatic
Tuning
0: Rotational Auto-tuning
VF:2
SLV:6
- O O X
1: Static Auto-tuning
2: Stator Resistance Measurement
3: Reserved
4: Loop Tuning
5: Rotational Auto-tuning
Combination (Item: 4+2+0)
Note
6: Static Auto-tuning Combination
(Item: 4+2+1)
Note
17-01 Motor Rated Output Power 0.00~600.00 - KW O O X
17-02 Motor Rated Current 0.1~1200.0 - A O O X
17-03 Motor Rated Voltage
200V: 50.0~240.0 -
V O O X
400V:100.0~480.0 -
17-04 Motor Rated Frequency 4.8~599.00 (Note8)
50.0/
60.0
Hz O O X
17-05 Motor Rated Speed 0~24000 KVA
*a
rpm O O X
17-06 Pole Number of Motor 2~16 (Even) 4 Pole O O X *6
17-07 Reserved