4-61
Group 17: IM Motor Automatic Tuning Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
17-08 Motor No-load Voltage
200V: 50~240
KVA
*a
V O O X
400V: 100~480
17-09 Motor Excitation Current
0.01~600.00
(15%~70% motor rated current)
KVA
*a
A O O X
1
17-10 Automatic Tuning Start
0: Disable
0 - O O X
1: Enable
17-11
Error History of Automatic
Tuning
0: No Error
0 - O O X
1: Motor Data Error
2: Stator Resistance Tuning Error
3: Leakage Induction Tuning Error
4: Rotor Resistance Tuning Error
5: Mutual Induction Tuning Error
6: Reserved
7: DT Error
8: Motor Acceleration Error
9: Warning
17-12 Leakage Inductance Ratio 0.1 ~ 15.0 3.4 % X O X
17-13 Slip Frequency 0.10 ~ 20.00 1.00 Hz X O X
17-14
Rotational Tuning Mode
Selection
0: VF Mode
1: Vector Mode
0 - O O X
Note1
*a: KVA means the default value of this parameter will be changed by different capacities of inverter.
1: It can be set when 17-00=1, 2, 6.
Group 18: Slip Compensation Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
18-00
Slip Compensation Gain at Low
Speed
0.00~2.50
VF:
0.00
- O O X *1
SLV:
1.00
18-01
Slip Compensation Gain at High
Speed
-1.00~1.00 0.0 - O O X *1
18-02 Slip Compensation Limit 0~250 200 % O X X
18-03 Slip Compensation Filter Time 0.0~10.0 1.0 Sec O X X
18-04
Regenerative Slip
Compensation Selection
0: Disable
0 - O X X
1: Enable
18-05 FOC Delay Time 1~1000 100 ms X O X
18-06 FOC Gain 0.00~2.00 0.1 - X O X