4-65
Group 23 Pump & HVAC Function Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
23-03
Maximum Pressure of
Pressure Transmitter
0.10 ~ 650.00 10.00 PSI O O O *6
23-04
Pump Pressure Command
Source
0: Set by 23-02
0 O O O
1: Set by AI
23-05 Display Mode Selection
0: Display of Target and Pressure
Feedback *
0 % O O O
1: Only Display Target Pressure
2: Only Display Feedback Pressure
23-06 Proportion Gain (P) 0.00~10.00 3.00 - O O O
23-07 Integral Time (I) 0.0~100.0 0.5 Sec O O O
23-08 Differential Time (D) 0.00~10.00 0.00 Sec O O O
23-09
Tolerance Range of Constant
Pressure
23-20=0 : 0.01 ~ 650.00
23-20=1 : 1~100
5
%/
PSI
O O O *6
23-10
Sleep Frequency of Constant
Pressure
0.00 ~ 599.00 (Note8) 30.00 Hz O O O
23-11
Sleep Time of Constant
Pressure
0.0 ~ 255.5 0.0 Sec O O O
23-12 Maximum Pressure Limit
23-20=0 : 0.00 ~ 650.00
23-20=1 : 0~100
50
%/
PSI
O O O *6
23-13
Warning Time of High
Pressure
0.0 ~ 600.0 10.0 Sec O O O
23-14 Stop Time of High Pressure 0.0 ~ 600.0 20.0 Sec O O O
23-15 Minimum Pressure Limit
23-20=0 : 0.00 ~ 650.00
23-20=1 : 0~100
5
%/
PSI
O O O *6
23-16 Warning Time of Low Pressure 0.0 ~ 600.0 0.0 Sec O O O
23-17
Fault Stop Time of Low
Pressure
0.0 ~ 600.0 0.0 Sec O O O
23-18
Time of Loss Pressure
Detection
0.0 ~ 600.0 0.0 Sec O O O
23-19
Proportion of Loss Pressure
Detection
0 ~ 100 0 % O O O
23-20
Switching of Pressure and
Percentage
0:Pressure
1 - O O O
Note4
1:Percentage
23-21
Reserved
23-22
Slave Trip Frequency
0.00 ~ 599.00 (Note8) 45.00 Hz O O O
Note2
23-23
Direction of Water Pressure
Detection
0: Upward Detection
1 - O O O
1: Downward Detection
23-24
Range of Water Pressure
Detection
23-20=0 : 0.00 ~ 65.00
23-20=1 : 0~10
1
%/
PSI
O O O *6
23-25
Period of Water Pressure
Detection
0.0 ~ 200.0 30.0 Sec O O O
23-26
Acceleration Time of Water
Pressure Detection
0.1 ~ 6000.0 KVA Sec O O O
23-27
Deceleration Time of Water
Pressure Detection
0.1 ~ 6000.0 KVA Sec O O O
23-28 Forced Run Command 0.00 ~ 599.00 (Note8) 0.00 Hz O O O