4-64
Group 22: PM Motor Parameters-
only available when PM Control Mode is selected
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
1: Enable
22-22
Fault History of SLV PM Motor
Tuning
0. No Error
0 -- X X O *4
1~4: Reserved
5: Circuit tuning time out.
6: Reserved
7: Other motor tuning errors
8: Reserved
9: Current Abnormity Occurs while
Loop Adjustment.
10: Reserved
11: Stator Resistance
Measurement Timeout
12: Reserved
22-25
Detection Mode Selection of
Default Magnetic Pole
0: Angle before Stop
2
(Note8)
-- X X O
Note4
1: Mode 1
2: Mode 2
22-26 Estimator Mode
0~1 (in PMSLV mode)
0 - X X O
Note6
22-27 Mode 2 Voltage Command
5~120
(Note8) (22-25=2 or 22-26=1is
enabled
)
50 % X X O
Note4
22-28
Mode 2 Frequency Division
Ratio
0~8
(Note8) (22-25=2 or 22-26=1is
enabled)
2 X X O
Note4
22-29
Field-Weakening Voltage
Control
80~110
(Note8)
95 % X X O
Note4
22-30 SPM Speed Estimation Gain
1~100
85 % X X O
Note6
22-31
SPM Speed Estimation Filter
Value
1~2000
60 HZ X X O
Note6
22-32 MTPA Selection
0: Disable
2 - X X O
Note8
1: Mode 1
2: Mode 2
3: Mode 3
22-33 MTPA Gain
0~400%
200 % X X O
Note8
22-34 IPM Estimator Gain
0.1~500.0
30.0 - X X O
Note8
22-35 IPM Estimator Compensation
0~300%
50 % X X O
Note8
Group 23 Pump & HVAC Function Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
23-00 Function Selection
0: Disable
0 - O O O
1: Pump
2: HVAC
3: Compressor *7
23-01
Setting of Single & Multiple
Pumps and Master & Slave
Machines
0: Single Pump
0 O O O
1: Master
2: Slave 1
3: Slave 2
4: Slave 3
23-02 Operation Pressure Setting 0.10 ~ 650.00 4.00 PSI O O O *6