4-76
00- 07
Main and Alternative Frequency Command Modes
Range
【0】:
Main reference frequency
【1】:
Main frequency + alternative frequency
When set to 0, the reference frequency is set by the main reference frequency selection of parameter
00-05. When set to 1, the reference frequency is sum of the main reference frequency (00-05) and
alternative frequency (00-06).
Note: The inverter will display the SE1 error when 00-07 = 1 and parameter 00-05 and 00-06 are set to the
same selection.
When parameter 00-06 is set to 0 (Keypad) the alternative frequency reference is set by parameter 05-01
(Frequency setting of speed-stage 0).
00- 08
Communication Frequency Command – READ ONLY
Range
【0.00~599.00】Hz
Display the frequency reference when 00-05 or 00-06 is set to communication control (3).
00- 09 Communication Frequency Command Memory
Range
【0】:
Do not store the communication frequency command at power down
【1】: Store communication frequency reference at power down
Note: This parameter is only effective in communication mode.
00-10
Minimum frequency detection
Range
【0】:Show warning if lower than minimum frequency
【1】:Run as minimum frequency if lower than minimum frequency
00-10=0:
When frequency command is lower than 01-08 (Minimum Output Frequency of Motor 1), it shows STP0
warning.
00-10=1:
When frequency command is lower than 01-08 (Minimum Output Frequency of Motor 1), inverter runs as
minimum output frequency of motor 1.
00- 11 Selection of PID Lower Limit Frequency
Range
【0】:
PID is bound to lower limit frequency when inverter sleeps.
【1】:
PID is bound to 0Hz when inverter sleeps.
When inverter gets to sleep,
00-11=0: PID is bound to lower limit frequency (00-13).
00-11=1: PID is bound to 0 Hz.
Note: Refer to descriptions of parameters 10-17~10-20 for details when inverter gets to sleep.