4-77
00-12
Upper Limit Frequency
Range
0.1~109.0%
Set the maximum frequency reference as a percentage of the maximum output frequency. Maximum
output frequency depends on motor selection.
Motor 1: Maximum frequency parameter 01-02.
Motor 2: Maximum frequency parameter 01-16.
00-13 Lower Limit Frequency
Range
0.0~109.0%
Set the minimum frequency reference as a percentage of the maximum output frequency. Maximum
output frequency depends on motor selection. Motor 1: Maximum frequency is set by parameter 01-02 and
Motor 2 Maximum frequency is set by parameter 01-16.
Notes:
- When the frequency lower limit is set to a value greater than 0 and the inverter is started the output
frequency will accelerate to the frequency lower limit with a minimum frequency defined by parameter
01-08 for motor 1 and parameter 01-22 for motor 2.
- Frequency upper limit has to greater or equal to the frequency lower limit otherwise the inverter will
display a SE01 (Set range error).
- Frequency upper and lower limit is active for all frequency reference modes.
Figure 4.4.5 Frequency reference upper and lower limits
Note: The maximum frequency setting in the keypad is according to parameter 01-02 (Maximum Output
Frequency) and 00-12 (Upper Frequency limit). The upper frequency limit is not over than 400Hz and
maximum limit for AI frequency is 100% to parameter 01-02.
00-14
Acceleration Time 1
Range
0.1~6000.0 Sec
00-15
Deceleration Time 1
Range
0.1~6000.0 Sec
00-16
Acceleration Time 2
Range
0.1~6000.0 Sec
00-17
Deceleration Time 2
Range
0.1~6000.0 Sec
00-21
Acceleration Time 3
Range
0.1~6000.0 Sec
00-22
Deceleration Time 3
Range
0.1~6000.0 Sec