4-80
time
time
time
Emergency stop
command
S5 ( 03- 04 =14 )
Run
command
Output
Frequency
ON OFF
ON
Emergency stop deceleration
time
100%
- 100%
-10V
10V
(20 mA)
0V
(4 mA)
Analog input
signal
( % )
( % )
-10V
10V
(20 mA)
0V
(4 mA)
Analog input
signal
(a) Forward Characteristics
(b) Reverse Characteristics
activated the inverter will decelerate to a stop using the time set in parameter 00-26.
Note: After an emergency stop command the run command and emergency stop command have to be
removed before the inverter can be restarted. Please refer to Figure 4.4.8. The emergency stop function
can be used to stop inverter in case of an external event.
Multi-function digital input terminals (03-00 ~ 03-05) set to 15: When the base block input is activated the
inverter output will turn off and the motor will coast to a stop.
Figure 4.4.8 Emergency stop example
00- 28
Selection of Main Frequency Command Characteristic
Range
【0】:
Positive characteristic (0~10V/4~20mA = 0~100%)
【1】: Negative / inverse characteristic (0~10V/4~20mA = 100~0%)
00-28= 0: Positive reference curve, 0 – 10V / 4 – 20mA = 0 – 100% main frequency reference.
00-28= 1: Negative reference curve, 0 – 10V / 4 – 20mA = 100 – 0% main frequency reference.
Note: Selection applies to analog input AI1 and AI2.
Note: AI2 will be useful for analog input frequency command when 04-05=0.
Figure 4.4.9 Positive/negative analog input as main frequency reference command.
00- 32
Application
Range
【0】:
General
【1】: Water supply pump
【2】: Conveyor
【3】:
Exhaust fan
【4】:
HVAC
【5】:
Compressor
【6】:
Reserved
【7】:
Reserved