4-81
Note: If set 00-32 back to 0, 2 wire initialization (60Hz)(230/400V) setting (13-08=11) will be executed.
Note: Before setting up 00-32 Application, it should do initialized setting (parameter 13-08) first. When
setting 00-32, the I/O port function changed automatically. To avoid accident,be sure to confirm the I/O
port signal of inverter and external terminal control
(1) Water supply pump
Parameter Name Value
00-00 Control mode selection 0 : V/F
00-14 Acceleration Time 1 2.0 sec
00-15 Deceleration Time 1 15.0 sec
11-00 Direction lock selection 1 : Forward direction only
01-00 V/F curve selection F
07-00
Momentary power loss/ fault restart
selection
1 : Enable
07-32 Speed Search Mode Selection 0 : Disable
08-00 Stall prevention function
xx0xb : Stall prevention is enabled in
deceleration
23-00 Function Selection 1: Pump
23-06 Proportion Gain (P) 2.00
23-07 Integral Time (I) 3.00 sec
23-26
Acceleration Time of Water Pressure
Detection
3.0 sec
23-27
Deceleration Time of Water Pressure
Detection
3.0 sec
10-03 PID Control Mode xxx1b: PID Enable
(2) Conveyor
Parameter Name Value
00-00 Control mode selection 0: V/F
00-14 Acceleration time 1 3.0 sec
00-15 Deceleration time 1 3.0 sec
07-32 Speed Search Mode Selection 0 : Disable
08-00 Stall prevention function
xx0xb: Stall prevention is enabled in
deceleration
(3)
Exhaust fan
Parameter Name Value
00-00 Control mode selection 0 : V/F
11-00 Direction lock selection 1 : Forward direction only
01-00 V/F curve selection F
07-00
Momentary power loss/ fault restart
selection
1 : Enable
07-32 Speed Search Mode Selection 1 : Enable
08-00 Stall prevention function
xx0xb : Stall prevention is enabled in
deceleration