4-82
(4)
HVAC
Parameter Name Value
00-00 Control mode selection 0 : V/F
11-00 Direction lock selection 1 : Forward direction only
11-01 Carrier frequency 8.0kHz
07-00
Momentary power loss/ fault restart
selection
1 : Enable
07-32 Speed Search Mode Selection 0 : Disable
10-03 PID Control Mode xxx1b: PID Enable
11-03 Automatic carrier frequency reduction 1 : Enable
01-00 V/F curve selection F
23-00 Function Selection 2: HVAC
(5) Compressor
Parameter Name Value
00-00 Control mode selection 0: V/F
00-02 Main Run Command Source Selection 1: External Terminal (Control Circuit)
00-05
Main Frequency Command
Source Selection
1: External Terminal (Analog AI1)
11-00 Direction lock selection 1: Forward direction only
00-14 Acceleration time 1 5.0 sec
00-15 Deceleration time 1 5.0 sec
01-06 Middle Output Frequency 1 Half of the maximum frequency
01-07 Middle Output Voltage 1 Half of the maximum voltage
07-00
Momentary power loss/ fault restart
selection
1: Enable
07-32 Speed Search Mode Selection 0: Disable
08-00 Stall prevention function
xx0xb: Stall prevention is enabled in
deceleration
23-00 Function Selection 3: Compressor
Note: 01-00 (V/F pattern) will hidden automatically.
(6) Reserved
(7) Reserved