4-95
01-14
Input Voltage Setting
Range
200V:【155.0~255.0】V
400V:【310.0~510.0】V
The minimum input voltage of inverter is 0.1V.
Set the inverter input voltage (E.g. 200V / 208V / 230V / 240V or 380V / 415V / 440V / 460V / 480V).
This parameter is used as a reference for predefined V/F curve calculation (01-00 = 0 to E), over-voltage
protection level, stall prevention, etc…
Note: It will depend on restore factory setting (13-08) to set the value of voltage
01-15
Torque Compensation Time
Range
【0
~10000】ms
Set the torque compensation delay time in milliseconds.
Only adjust in the following situations:
Increase value when:
When experiencing motor vibration
Decrease value when:
When motor torque response is too slow