Group 02-IM Motor Parameter
02- 00
No-load Current
Range
0.01~600.00A
02- 01
Rated Current
Range
25%~200% of inverter’s rated current.
02-03
Rated Rotation Speed
Range
0~60000rpm
02- 04
Rated Voltage
Range
200V:50.0~240.0V
400V: 100.0~480.0V
02- 05
Rated Power
Range
0.01~600.00KW
02-06
Rated Frequency
Range
4.8~599.0Hz
02-07
Poles
Range
2~16(Even)
02-09
Excitation Current <1>
Range
15.0~70.0%
02-10
Core Saturation Coefficient 1 <1>
Range
0~100%
02-11
Core Saturation Coefficient 2 <1>
Range
0~100%
02-12
Core Saturation Coefficient 3 <1>
Range
80~300%
02-13
Core Loss
Range
0.0~15.0%
02-15
Resistance between Wires
Range
0.001~60.000
02-19
No-Load Voltage
Range
200V:50~240V
400V:100~480V
02-33
Leakage Inductance Ratio <1>
Range
0.1~15.0%
02-34
Slip Frequency <1>
Range
0.1~20.0Hz
In most case no adjustment is required after performing an auto-tune except when using the inverter in
special applications (e.g. machine tool, positioning, etc…).
Please refer to parameter group 22 for permanent magnet motor parameters.
(1) Number of motor poles (02-07)
Set the number of motor pole according to the motor nameplate.
(2) Motor rated power (02-05)
Set the motor power according to the motor nameplate.
(3) Motor rated current (02-01)
Set the motor rated current according to the motor nameplate.