Group 02-IM Motor Parameter
02- 00
No-load Current
Range
【0.01~600.00】A
02- 01
Rated Current
Range
25%~200% of inverter’s rated current.
02-03
Rated Rotation Speed
Range
【0~60000】rpm
02- 04
Rated Voltage
Range
200V:【50.0~240.0】V
400V: 【100.0~480.0】V
02- 05
Rated Power
Range
【0.01~600.00】KW
02-06
Rated Frequency
Range
【4.8~599.0】Hz
02-07
Poles
Range
【2~16】(Even)
02-09
Excitation Current <1>
Range
【15.0~70.0】%
02-10
Core Saturation Coefficient 1 <1>
Range
【0~100】%
02-11
Core Saturation Coefficient 2 <1>
Range
【0~100】%
02-12
Core Saturation Coefficient 3 <1>
Range
【80~300】%
02-13
Core Loss
Range
【0.0~15.0】%
02-15
Resistance between Wires
Range
【0.001~60.000】Ω
02-19
No-Load Voltage
Range
200V:【50~240】V
400V:【100~480】V
02-33
Leakage Inductance Ratio <1>
Range
【
0.1~15.0】%
02-34
Slip Frequency <1>
Range
【
0.1~20.0】Hz
In most case no adjustment is required after performing an auto-tune except when using the inverter in
special applications (e.g. machine tool, positioning, etc…).
Please refer to parameter group 22 for permanent magnet motor parameters.
(1) Number of motor poles (02-07)
Set the number of motor pole according to the motor nameplate.
(2) Motor rated power (02-05)
Set the motor power according to the motor nameplate.
(3) Motor rated current (02-01)
Set the motor rated current according to the motor nameplate.