4-99
Group 03- External Digital Input and Output Parameters
03- 00
Multi-function terminal function setting – S1
03- 01 Multi-function terminal function setting – S2
03- 02 Multi-function terminal function setting – S3
03- 03
Multi-function terminal function setting – S4
03- 04
Multi-function terminal function setting – S5
03- 05 Multi-function terminal function setting – S6
Range
【0】: 2-Wire Sequence (ON: Forward Run Command)
【1】: 2-Wire Sequence (ON: Reverse Run Command)
【2】: Multi-Speed Setting Command 1
【3】: Multi-Speed Setting Command 2
【4】: Multi-Speed Setting Command 3
【5】: Multi-Speed Setting Command 4
【6】: Forward Jog Run Command
【7】: Reverse Jog Run Command
【8】: UP Frequency Increasing Command
【9】: DOWN Frequency Decreasing Command
【10】: Acceleration/ Deceleration Setting Command 1
【11】: Acceleration/ Deceleration Inhibition Command
【12】: Main/Alternative Run command Switching
【13】: Main/Alternative Frequency Command Switching
【14】: Emergency Stop (Decelerate to Zero and Stop)
【15】: External Baseblock Command (Rotation freely to Stop)
*1
【16】: PID Control Disable
【17】: Fault Reset (RESET)
【18】: Reserved
【19】: Speed Search 1(from the maximum frequency)
*1
【20】: Manual Energy Saving Function
【21】: PID Integral Reset
【22】~【23】: Reserved
【24】: PLC Input
【25】: External Fault
【26】: 3-Wire Sequence (Forward/ Reverse Command)
【27】: Local/ Remote Selection
【28】: Remote Mode Selection
【29】: Jog Frequency Selection
【30】: Acceleration/ Deceleration Setting Command 2
【31】: Inverter Overheating Warning
【32】: Reserved
【33】: DC Braking*
1
【34】: Speed Search 2 (from Frequency Command)*
1
【35】: Timing Function Input
【36】: PID Soft Start Disable
【37】~【40】: Reserved
【41】: PID Sleep
【42】~【46】: Reserved
【47】: Fire Mode (Forced to Run Mode)
【48】: KEB Acceleration
【49】: Parameters Writing Allowable
【50】: Unattended Start Protection (USP)
【51】~【52】: Reserved
【53】: 2-Wire Self Holding Mode (Stop Command)