4-102
Value
Function
Description
Control mode
Name LCD Display V/F SLV
PM
SLV
20
Manual Energy
Saving Function
Energy saving
ON: Manual energy saving control is
based on the settings of 11-12 and
11-18.
O X X
21 PID Integral Reset PID I-Reset ON: PID integral value reset O O O
22~23 Reserved Reserved Reserved - - -
24 PLC input PLC Input ON: Digital PLC input O O O
25 External fault Ext. Fault ON: External fault alarm O O O
26
3-Wire Sequence
(Forward/ Reverse
Command)
3-Wire
(FWD/REV)
3-wire control (forward/reverse
command). ON: Reverse; OFF: Forward.
When the parameter is set to 26terminal
S1 and terminal will become operation
command and stop command
respectively, and their original functions
will be closed.
O O O
27
Local/ Remote
Selection
Local/Remote
ON: Local mode (via the digital operator)
OFF: Frequency command and operation
command will be determined according to
the setting of parameter (00-02 and
00-05)
O O O
28
Remote Mode
Selection
Remote Mode
Sel
ON: RS-485 communication
OFF: Control circuit terminal
O O O
29
Jog Frequency
Selection
JOG Freq Ref ON: Selection jog frequency command O O O
30
Acceleration/
Deceleration
Setting Command
2
A
cc/Decel Time
Selection 2
Acceleration/deceleration time selection
command2
O O O
31
Inverter
Overheating
Warning (OH2)
Overheat Alarm
ON: Inverter overheat alarm (OH2)
input( will display OH2)
O O O
32 Reserved Reserved Reserved - - -
33 DC Braking
DC Brake
Command
ON: Perform DC braking O X X
34
Speed Search 2
(from Frequency
Command)
Speed Search
2
ON: Search speed from set frequency O X O
35
Timing Function
Input
Timer Input
.Set the time function at 03-37, 03-38
.Set the time function output at 03-11,
03-12
O O O
36
PID Soft Start
Disable
PID SFS
Disable
ON: PID slow-start off O O O
37~40
Reserved
Reserved
Reserved
- - -
41 PID Sleep PID Sleep ON: PID Sleep O O O
42~46
Reserved
Reserved
Reserved
- - -
47
Fire Mode (Forced
to Run Mode)
Fire Mode
ON: Inverter runs in the max. frequency of
motor 1 (parameter 01-02).
Note: If fault message of OC, SC, CUV,
FUL, STO occur, function of fire mode will
stop.
O O O
48 KEB Acceleration KEB Accel. ON: KEB acceleration start O X X
49
Parameters
Write-in Allowed
Write Enabled
ON: All parameters are writable.
OFF: Except reference frequency (00-05)
all parameters are write-protected.
O O O