4-104
Table 4.4.5 Multi-speed operation selection
Speed
Multi-function digital input (S1 ~ S6)
Frequency selection
Jog
frequency
reference
Multi-speed
frequency
4
Multi-speed
frequency
3
Multi-speed
frequency
2
Multi-speed
frequency
1
1 0 0 0 0 0
Frequency command 0 ( 05-01) or
main speed frequency
*2
2 0 0 0 0 1
(04-05=0) Auxiliary speed frequency
or (04-05≠0) Frequency command 1
(05-02)
*3
3 0 0 0 1 0
Frequency command 2 (05-03)
4 0 0 0 1 1
Frequency command 3 (05-04)
5 0 0 1 0 0
Frequency command 4 (05-05)
6 0 0 1 0 1
Frequency command 5 (05-06)
7 0 0 1 1 0
Frequency command 6 (05-07)
8 0 0 1 1 1
Frequency command 7 (05-08)
9 0 1 0 0 0
Frequency command 8 (05-09)
10 0 1 0 0 1
Frequency command 9 (05-10)
11 0 1 0 1 0
Frequency command 10 (05-11)
12 0 1 0 1 1
Frequency command 11 (05-12)
13 0 1 1 0 0
Frequency command 12 (05-13)
14 0 1 1 0 1
Frequency command 13 (05-14)
15 0 1 1 1 0
Frequency command 14 (05-15)
16 0 1 1 1 1
Frequency command 15 (05-16)
17 1
*1
─ ─ ─ ─
Jog frequency command (00-18)
0: OFF, 1: ON, ─: Ignore
*1. Jog frequency terminal has a higher priority than multi-speed reference 1 to 4.
*2. When parameter 00-05=0 (frequency reference input = digital operator), multi-speed frequency 1 will be
set by 05-01 frequency reference setting1). When parameter 00-05=1 (frequency reference input=control
circuit terminal), multi-speed frequency command 1 is input through analog command terminal AI1 or
AI2.
*3. 05-02 is used for auxiliary speed frequency of AI2 as default setting. It is necessary to set 04-05≠0 to
switch 05-02 to be for Frequency command 1.
When PID control mode is enabled (10-03= xxx1b),
Frequency of Speed - Stage 1 can not switch auxiliary speed frequency even though Multi-function
Terminal Function Setting (03-00~03-05)=16 (PID control disable).
Wiring Example: Fig. 4.4.14 and 4.4.15 show an example of a 9-speed operation selection.
Figure 4.4.14 Control Terminal Wiring Example