4-105
Figure 4.4.15 9-speed timing diagram
*1. When 00-05=1, multi-speed frequency reference is set by analog input AI1 or AI2.
03-0X =06: Forward jog run command, uses jog frequency parameter 00-18.
03-0X =07: Reverse jog run command, uses jog frequency parameter 00-18.
Notes:
- To excute the Forward jog or Reverse jog command need to set 00-02=1 at first.
- Jog command has a higher priority than other frequency reference commands.
- Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms.
- When 11-00 (Direction Lock Selection) set to 1 (Only Allow Forward Rotation), if there is a motor
reverse command, the “RUNER” warning will display.
- When 11-00 (Direction Lock Selection) set to 2 (Only Allow Reverse Rotation), if there is a motor
forward command, the “RUNER” warning will display.
03-0X =08: UP frequency accelerating command; set parameter 00-05 Frequency command to 2 to
activate.
03-0X =09: Down frequency decelerating command; set parameter 00-05 Frequency command to 2 to
activate.
Note:
- The inverter operates the variation of increasing/ decreasing output frequency via keypad (refer
to parameter 11-56) / external multi-function digital input (terminal S1to S6) when the motor is
running.