4-114
03- 09 Multi-function Terminal S1-S4 Type Selection
Range
xxx0b】:S1 A contact xxx1b】:S1 B contact
xx0xb】:S2 A contact xx1xb】:S2 B contact
x0xxb】:S3 A contact x1xxb】:S3 B contact
0xxxb】:S4 A contact 1xxxb】:S4 B contact
03- 10 Multi-function Terminal S5-S6 Type Selection
Range
xxx0b】:S5 A contact xxx1b】:S5 B contact
xx0xb】:S6 A contact xx1xb】:S6 B contact
Parameter 03-09 and 03-10 selects the digital input type between a normally open and a normally closed
switch/contact.
Each bit of 03-09/03-10 presents an input
03-09= 0 0 0 0 0normally open switch
s4 s3 s2 s1 1normally closed switch
03-10= x x 0 0 0normally open switch
s6 s5 1normally closed switch
Example: S1 and S2 wired to a normally closed contact / switch set 03-09=0011.
Do not set the operation command parameter 00-02 to terminal control before setting the digital
input type. Failure to comply may cause death or serious injury.
03-11
Relay (R1A-R1C) Output
03-12 Relay (R2A-R2C) Output
03-20
Relay(R4A-R4C) Output *1
03-21
Photo-coupler(DO2-DOG) Output *1
03-39
Relay (R3A-R3C) Output
Range
0: During Running
1: Fault Contact Output
2: Frequency Agree
3: Setting Frequency Agree (03-13±03-14)
4: Frequency Detection 1 ( 03-13 + 03-14)
5: Frequency Detection 2 ( 03-13)
6: Automatic Restart
7~8: Reserved
9: Baseblock
10~11】:Reserved
12: Over-Torque Detection
13: Current Agree
14: Mechanical Brake Control (03-17~18)
15~17: Reserved
18: PLC Status
19: PLC Control
20: Zero Speed
21: Inverter Ready
22: Undervoltage Detection
23: Source of Operation Command
24:Source of Frequency Command
25: Low Torque Detection
26: Frequency Reference Missing
27: Timing Function Output
28~31: Reserved