4-115
32: Communication Control Contacts
33: RTC
Timer 1
34: RTC Timer 2
35: RTC Timer 3
36: RTC Timer 4
37: Detection Output of PID Feedback Loss
38: Brake Release
42: Over-High Pressure
43: Over-Low Pressure
44: Loss of Pressure Detection
45: PID Sleep
46: Over-High Flow
47: Over-Low Flow
48: Shortage of Low Suction
49: Communication Error
50: Frequency Detection 3 ( 03-44+03-45)
51: Frequency Detection 4 ( 03-44)
52: Frequency Detection 5 ( 03-46+03-47)
53: Frequency Detection 6 ( 03-46)
54: Turn on short-circuit braking
57: Low Current Detection
58: Frequency Deceleration Detection
59: Overheat Detection
*1: The parameters are available when the I/O expansion card installed.
Default function Related parameter
During
Running
Fault signal
03-11
03-12
R1B
R1C
R2A
R2C
R1A
R3A
R3C
Zero
Speed
03-39
Figure 4.4.22 Multi-function digital output and related parameters
Table 4.4.6 Description of multi-function digital output
Value
Function
Description
Control Mode
Name LCD Display V/F SLV
PM
SLV
0 During Running Running ON: During running (Run Command is ON) O O O
1
Fault Contact
Output
Fault
ON: Fault contact output (except CF00 and
CF01 )
O O O
2
Frequency
Agree
Freq. Agree
ON: Frequency agree (frequency agree width
detection is set by 03-14 )
O O O
3
Setting
Frequency
Agree
Setting Freq
Agree
ON: Output frequency = allowed frequency
detection level (03-13) ± frequency
bandwidth (03-14)
O O O
4
Frequency
Detection 1
Freq. Detect 1 ON: Output frequency 03-13 + 03-14 O O O
5
Frequency
Detection 2
Freq. Detect 2 OFF: Output frequency 03-13 + 03-14 O O O