4-118
03-1X=3: Setting Frequency Agree
Output is active when the output frequency falls within the frequency detection width (03-14) of the set
frequency detection level (03-13).
03-1X=4: Frequency detected 1
Output is active when the output frequency rises above the frequency detection level (03-13) + frequency
detection width (o3-14) and deactivates when the output frequency falls below frequency detection level
(o3-13).
03-1X=5: Frequency detected 2
Output is active when the output frequency is below the frequency detection level (03-13) + frequency
detection width (03-14) and turns off when the output frequency falls below frequency detection level.
Refer to parameter group 03 for frequency detection function.
03-1X=6: Automatic restart.
Output is active during an auto-restart operation.
03-1X=9: Baseblock (B.B.)
Output is active when the inverter output is turned off during a Baseblock command.
03-1X=12: Over torque detected (Normally Open)
Output is active during an over torque detection see parameters 08-13 ~ 08-16.
03-1X=25: Low torque detected (Normally Open)
Output is active during low torque detection see parameters 08-17 ~ 08-20.
03-1X=13: Current Agree
When the output current is larger than that in 03-15 and its duration is higher than that in 03-16, this
function will be ON.
03-1X=18: PLC status (setting =18)
Output is active when operation command parameter (00-02) is set to 3: PLC Control.
03-1X=19: PLC control contact
Output is controlled by the PLC logic
03-1X=20: Zero-speed
Output is active during zero-speed
Active Output frequency >=minimum output frequency (01-08, Fmin)
Off Output frequency is <=the minimum output frequency