4-117
Value
Function
Description
Control Mode
Name LCD Display V/F SLV
PM
SLV
38 Brake Release Brake Relase ON: Brake Release X O X
42
Over-High
Pressure
High PSI ON:High PSI Warning/Fault O X X
43
Over-Low
Pressure
Low PSI ON: Low PSI Warning/Fault O X X
44
Loss of
Pressure
Detection
Fb PSI ON: Fb PSI Fault O X X
45 PID Sleep PID Sleep ON: During PID Sleep O O O
46 Over-High Flow Over GPM ON: Over GPM Warning/Fault O O O
47 Over-Low Flow Low GPM ON: Low GPM Warning/Fault O O O
48
Shortage of Low
Suction
Low Suction ON: Low Suction Warning/Fault O O O
49
Communication
Error
RS-485 Err. ON: Communication Error Warning O O O
50
Frequency
Detection 3
Freq. Detect 3
ON: output frequency > 03-44,Hysteresis
range :03-45
O O O
51
Frequency
Detection 4
Freq. Detect 4
OFF: output frequency > 03-44,Hysteresis
range :03-45
O O O
52
Frequency
Detection 5
Freq. Detect 5
ON: output frequency > 03-46,Hysteresis
range :03-47
O O O
53
Frequency
Detection 6
Freq. Detect 6
OFF: output frequency > 03-46,Hysteresis
range :03-47
O O O
54
Turn on
short-circuit
braking
SC Brk
ON: Turn on short-circuit breaking
X X O
57
Low Current
Detection
Low Current
Detect
ON: Output Current ≦ 03-48 Low current
detection level
O O O
58
Frequency
Deceleration
Detection
Freq. Decel to
ON: Output Frequency < Frequency
Command – parameter 03-14 in
deceleration
O O O
59 OH Detection OH Detect
ON: Heat Sink Fin Temperature >08-46,
hysteresis Zone 08-47
O O O
03-1X=0: During Running
OFF Run command is OFF and the inverter is stopped.
ON Run command is ON or output frequency is greater than 0.
03-1X=1: Fault contact output
Output is active during fault condition.
Note: Communication error (CF00, CF01) do not activate the fault contact.
03-1X=2: Frequency Agree
Output is active when the output frequency falls within the frequency reference minus the frequency
detection width (03-14).