4-125
Timing Diagram:
03-49
Constant
100msec
03-48
03-11
Relay
ON
I Load Current
100%
T
Operation
Command
ON
The continuous time set
by parameter 03-49 is not
reached, the relay is
disabled.
03-17 Setting of Mechanical Brake Release Level
Range
0.00~599
.00 Hz
03-18 Setting of Mechanical Brake Operation Level
Range
0.00~599
.00 Hz
When 03-11=14,
Relay output starts at acceleration if the output frequency reaches the mechanical brake release level
(03-17).
Relay output stops at deceleration if the output frequency reaches the mechanical brake operation level
(03-18).
When 03-17≤03-18, timing diagram is as follows:
03-17
03-18
03-11=14
Operation
Hz
T
ON OFF
RUN STOP