4-126
When 03-17≥03-18, timing diagram is as follows:
03-18
03-17
Operation
03-11=14
Hz
T
ON
OFF
RUN STOP
03- 19 Relay (R1A-R3C) Type
Range
【xxx0b】: R1A normally open 【xxx1b】: R1A normally close
【xx0xb】: R2A normally open 【xx1xb】: R2A normally close
【x0xxb】: R3A normally open 【x1xxb】: R3A normally close
【x0xxb】: R4A normally open 【x1xxb】: R4A normally close *1
03- 29
Photo-coupler Output Selection (DO2-DOG) *1
Range
【xx0xb】: Photo-coupler 2 A Contact 【xx1xb】: Photo-coupler 2 B Contact
*1: The parameters are available when the I/O expansion card installed.
Parameter 03-19 selects the digital output type between a normally open and a normally closed contact.
Each bit of 03-19 presents an output:
03-19= 0 0 0 0 0: normally open contact
R3 R2 R1 1: normally close contact
Example: R1 normally closed and R2 normally open contact set 03-19=x001b.
03- 27 UP/DOWN Frequency Hold/ Adjust Selection
Range
【
0】: Keep UP/DOWN frequency when stopping.
【1】: Clear UP/DOWN frequency when stopping.
【2】: Allow frequency UP/DOWN when stopping.
【3】: Refresh frequency at acceleration.
03-27=0: When the run command is removed the UP/DOWN frequency reference before deceleration is
stored. The next time the run command is applied the output frequency will ramp up to the previously stored
frequency reference.
03-27=1: When the run command is removed the UP/DOWN frequency reference command is cleared (set
to 0). The next time the run command is applied the output frequency will start at 0.
03-27=2: UP/DOWN command is active when run command is not active.
03-27=3: Keep the state of frequency command not to be cleared. When Run Command re-sends, press
UP/DOWN key before the run frequency reaches the frequency command, press UP/ DOWN key, then:
- When 03-40 = 0, Frequency Command is set by Run Frequency.
- When 03-40≠0, Frequency Command is set by the values of Run Frequency plus the setting frequency
of 03-40.