4-142
Figure 4.4.36 Stall prevention level adjustment during operation
04-05/04-10=8: Frequency lower limit
Multi-function analog input AI2/AI3 can be used to adjust the lower limit of frequency reference.
Maximum output frequency (Fmax, 01-02) = 100%. The actual lower limit is determined by the maximum
value of 00-13 (frequency lower limit) and level of the multi-function analog input AI2/AI3.
Figure 4.4.37 Adjustment of lower limit of frequency reference