4-143
04-05/04-10=9: Jump frequency 4
Multi-function analog input AI2/AI3 can be used to adjust Jump frequency 4.
Maximum output frequency (01-02, Fmax) = 100%. Setting 11-08 ~ 11-10 to 0.0Hz turns of the Jump
frequency function.
Figure 4.4.38 Jump frequency 4 setting operation
04-05=10 or 04-10=10: Added to AI1
Multi-function analog input AI2/AI3 can be used as a bias level for analog input AI1.
Figure 4.4.39 Added to Al1 as a bias operation
Example:
04-02 (AI1 gain) = 100%, 04-03 (AI2 gain) = 0%, and terminal AI2 level is 2V. If input terminal AI1 is 0V,
the internal reference frequency of terminal AI1 will be 20 %
04-05=11: Positive torque limit
Multi-function analog input AI2 can be used to adjust the positive torque limit.
04-05=12: Negative torque limit
Multi-function analog input AI2 can be used to adjust the negative torque limit.
04-05=13: Regenerative torque limit
Multi-function analog input AI2 can be used to adjust the regenerative torque limit.