4-144
04-05=14: Positive / negative torque limits
Multi-function analog input AI2 can be used to adjust both the positive and negative torque limit.
For more details on torque limits, please refer to parameter group 21 - torque control group.
04-05=15: Reserved
04-05=16: Torque compensation of speed control
Multi-function analog input AI2 can be used to adjust the torque compensation in closed loop vector mode.
For more details on the torque control functions, please refer to parameter group 21 - torque control group.
04-11
AO1 Function Setting
Range
0:
Output Frequency
1: Frequency Command
2:
Output Voltage
3:
DC Voltage
4:
Output Current
5:
Output Power
6:
Motor Speed
7: Output Power Factor
8: AI1 Input
9: AI2 Input
10:
Torque Command
11: q-axis Current
12: d-axis Current
13: Speed Deviation
14:
Reserved
15:
ASR Output
16:
Reserved
17:
q-axis Voltage
18: d-axis Voltage
19~20: Reserved
21: PID Input
22: PID Output
23: PID Target Value
24: PID Feedback Value
25: Output Frequency of the Soft Starter
26: Reserved
27: Reserved
28: Communication Control
04-12
AO1 Gain
Range
0.0~1000.0%
04-13
AO1 Bias
Range
-100.0~100.0%
04-16
AO2 Function Setting
Range
Setting range and definition are the same as those of 04-11.
04-17
AO2 Gain
Range
0.0~1000.0%
04-18
AO2 Bias
Range
-100.0~100.0%
04-19
AO Output Signal Type