4-145
Range
0: AO1 0~10V AO2 0~10V
1: AO1 0~10V AO2 4~20mA
2: AO1 4~20mA AO2 0~10V
3: AO1 4~20mA AO2 4~20mA
For the analog output and related parameters, refer to Fig.4.4.40.
Figure 4.4.40 Analog outputs and related parameters
Analog output AO1 and AO2 adjustment (04-12, 04-13 and 04-17, 04-18)
Signal: Use parameter 04-11 to select the analog output signal for AO1 and parameter 04-16 to select the
analog output signal for AO2.
Gain: Use parameter 04-12 to adjust the gain for AO1 and parameter 04-17 to adjust the gain for AO2.
Adjust the gain so that the analog output (10V/20mA) matches 100% of the selected analog output signal
(04-11 for AO1 and 04-16 for AO2).
Bias: Use parameter 04-13 to adjust the bias for AO1 and parameter 04-18 to adjust the bias for AO2.
Adjust the bias so that the analog output (0V/4mA) matches 0% of the selected analog output signal
(04-11 for AO1 and 04-16 for AO2).
Figure 4.4.41 Analog output level adjustment