4-146
Table 4.4.9
Selection of analog output terminals function (04-11 and 04-16)
04-11, 04-16
Parameter setting
Function
(Keypad display)
Monitoring Parameters
Group 12
Control Mode
VF SLV
PM
SLV
0 Output Freq 12-17
O O O
1 Freq Ref 12-16
O O O
2 Output Voltage 12-19
O O O
3 DC Voltage 12-20
O O O
4 Output Current 12-18
O O O
5 Output KW 12-21
O O O
6 Motor Speed 12-22
O O O
7 Output PF 12-23
O O O
8 AI1 Input 12-25
O O O
9 AI2 Input 12-26
O O O
10 Torque Ref 12-27 X
O O
11 Current Iq 12-28 X
O O
12 Current Id 12-29 X
O O
13 Speed Deviation 12-30 X
O O
14 Reserved -
X X X
15 ASR Output 12-32
X X X
16 Reserved -
X X X
17 Voltage Ref Vq -
X O O
18 Voltage Ref Vd -
X O O
19~20 Reserved -
X X X
21 PID Input 12-36
O O O
22 PID Output 12-37
O O O
23 PID Setpoint 12-38
O O O
24 PID Feedback 12-39
O O O
25 Output Freq (SFS) -
O O O
26~27 Reserved -
X X X
28 Comm Control -
O O O
04-20
Filter Time of AO Signal Scan *1
Range
【0.00~0.50】Sec
*1: It is new added in inverter software V1.4.
This function is used for filtering out momentary change of analog output signal.
Note: When this function is added, it will decrease the system reaction but increase interference
protection.